An open cooling tower rejects heat by bringing circulating tower water into direct contact with outdoor air. It can serve industrial processes and condenser-water loops where the project can support water treatment, makeup water, drainage and routine maintenance.


Crossflow vs counterflow open cooling towers
In a crossflow tower, air moves horizontally across descending water. Many crossflow models use gravity-fed distribution basins. In a counterflow tower, air travels upward against descending water. Factory-assembled counterflow models often use spray nozzles, so confirm the pressure the selected model requires.
| Selection factor | Crossflow | Counterflow |
|---|---|---|
| Air path | Horizontal through the fill | Upward through the fill |
| Water distribution | Often gravity-fed basins | Often pressurized spray nozzles |
| Layout check | Keep side inlets and basin inspection access clear | Verify inlet clearance, discharge recirculation and nozzle access |
| Pump and service check | Confirm basin elevation and distribution requirements | Include required nozzle pressure and check the spray header service route |
Compare the HACST crossflow open cooling tower and counterflow open cooling tower at the same heat load, water flow, temperatures and design wet-bulb. Ask for the actual footprint and sound data for the selected models.


Where an open tower fits
- Chiller condenser-water loops. The tower cools the water circulating through a separate condenser. The refrigerant stays in the chiller circuit.
- Industrial process cooling. Use direct tower water where the equipment and water program allow it. An intermediate heat exchanger can isolate a sensitive process loop.
- Plants with changing loads. Check how the selected tower distributes water when cells are staged and how operators will clean and inspect the basin and fill.


What to confirm before selection
Provide the design duty, flow, entering and leaving temperatures, wet-bulb, elevation and site layout. Include water quality and treatment, sound limits and minimum winter load. Start with the industrial cooling tower sizing guide, compare open cooling tower models, or send us your design conditions.